IVECO Aifo Series 30-450 KVA

  • Continuos ratings are suitable for continuous elettrical poer (at variable load) without limitation to annual hours of operation, a 10% overload for 1 hour is available.
  • Stanby rating are applicable to supplying continuous elettrical power (at variable load) in the event of a utility power failure without limitation to the annual hours, no overload is permitted on these ratings.
  • All the brake horsepower KWm are to BS 5514, ISO 3046 and A.B.G.S.M. "C" test condition.
  • For site condition exceeding the above standard, a derating may be applicable in accordance with IVECO-AIFO publication.
  • The generating set apparent power (KVA) depends on the power factor (cosfi) (KVA=KW/cosfi). For above generator output a power factor of 0,8 is assumed.
  • The dimensions of the soundpoofed generators refer to a residual nouse of about 65-70 dBA measured at a distance of 7 meters in an open field as standard ISO.
 

POWER SELECTION 50HZ/1500 R.P.M. POWER SELECTION 60HZ/1800 RPM
Genset
Model
Contin. rating Stand by rating. Tecnical data Contin. rating Stand by rating.
KW KVA KW KVA KWm
1500 RPM
Model KWm
1800 RPM
KW KVA KW KVA
Cont. Emerg. Cont. Emerg.
IA30 24 30 27 33 29 32 8021I.05 33 36 28.5 35 31 40
IA40 32 40 34 42 36 39 8041I.05 43 48 38 47 42 53
IA50 40 50 45 56 45 51 7450I.15 50 56 45 56 50 63
IA60 48 60 55 66 56.5 62 8061I.25 63 69 57 71 62 77.5
IA70 56 70 60 77 63 69 7450SI.15 72 79 62 77.5 70 87.5
IA80 64 80 70 88 71 79 7451SI.16 85 93 75 94 83 104
IA100 80 100 91 115 88 101 8061SI.16 106 119 95 120 108 135
IA130 107 130 120 150 114 132 8061SRI.25 127 140 116 145 128 160
IA150 120 150 131 165 131 144 8361SRI.25 151 165 138 172 150 187
IA210 170 210 188 235 185 205 8361SRI.26 200 220 185 231 205 255
IA250 200 250 223 278 221 243 8210SRI.25 239 263 222 278 245 306
IA300 240 300 268 335 264 291 8210SRI.26 288 320 265 330 295 370
IA350 280 350 310 387 306 337 8210SRI.27 313 344 288 360 320 400
IA380 304 380 334 418 322 361 8210SRI.28 341 370 312 390 344 430
IA400 320 400 351 438 348 382 8281SRI.26 391 433 365 455 403 537
IA450 340 450 400 500 390 430 8281SRI.27 400 440 370 460 410 510

DIMENSIONS AND WEIGHTS
Genset
Model
GENSET STANDARD
DIMENSIONS IN mm
SOUNDSHIELD GENSET
DIMENSIONS IN mm
Lenght* Width Hight Weight *kg. Lenght* Width Hight Weight *kg.
IA30 1450 800 1270 700 2460 1100 1550 1250
IA40 1700 800 1270 750 2460 1100 1550 1300
IA50 1800 800 1300 830 2460 1100 1550 1450
IA60 2000 800 1350 950 3270 1100 1550 1950
IA70 1900 800 1400 900 *2710 1100 1550 1900
IA80 1900 800 1400 1055 *2710 1100 1550 2100
IA100 2100 850 1150 1100 3870 1300 1965 2100
IA130 2200 850 1370 1150 3870 1300 1965 2150
IA150 2600 950 1650 1500 3870 1300 1965 2500
IA210 2600 950 1650 1550 3870 1300 1965 2550
IA250 2900 1300 1600 2200 4470 1480 2225 4200
IA300 *3000 *1300 *1600 2400 4470 1480 2225 4250
IA350 3000 1300 2100 2600 4670 1900 2420 4700
IA380 3100 1300 2100 2650 4670 1900 2420 47500
IA400 3000 1550 2000 2800 4670 1900 2420 5000
IA405 3000 1550 2000 2950 4670 1900 2420 5100
All descriptions and illustrations in this catalogue are given purely as a guide and are not binding.

* Start battery not included
* Total weight dry



Copyright © 2000 - F.lli Stamegna s.n.c.